Soffit Sprinkler Placement
Enter the width and height of the soffit to find required sprinkler placement. Supports NFPA 13-2019 Chapter 10 standard spray and Chapter 12 residential sprinklers — pendent, upright, and sidewall orientations.
Minimum distance from wall to sprinkler
1' 8"
Place the sprinkler at least 1' 8" from the wall.
NFPA 13-2019 Figure 10.2.7.1.2(b)
Calculation
- Formula
- A = D − 8″ + B
- Soffit width (D)
- 24″
- Soffit below deflector (B)
- 4″
- Computation
- 24″ + 4″ − 8″ = 20″
- Required A
- 20″
Inputs
- Sprinkler standard
- Standard spray (NFPA 13 Ch. 10)
- Orientation
- Pendent / upright
- Soffit width (D)
- 2'
- Soffit below deflector (B)
- 4"
- Method
- Formula
- Reference
- NFPA 13-2019 Figure 10.2.7.1.2(b)
Notes
- NFPA 13-2019 Figure 10.2.7.1.2(c) allows an obstruction against the wall up to 24″ wide with no additional protection beneath it, and with no limit on how far it hangs down, where the sprinkler is within ½ S of the wall. Check the sprinkler's spacing before relying on it.
- Required distance A is less than the soffit width D, so a sprinkler placed at the minimum A would fall under the soffit rather than hang from the open ceiling. Verify placement against the under-soffit sprinkler rules for this soffit width.